Autotransformer Closed Transition Start Type

Request more information about this product


Series MP450 - Combined Manual Automatic

Metron Fire Pump Controllers conform to the latest requirements of Chapter 7, National Fire Protection Association Pamphlet 20, Standard for Centrifugal Fire Pumps as adopted by Underwriters' Laboratories and Factory Mutual. They are withstand rated and listed by Underwriters' Laboratories and approved by Factory Mutual Research Corporation.

Sizes range from 15 to 600 horsepower, 200 to 600 volts, 60 Hz. These controllers are for use on Reduced Voltage type installations.

To assure the best possible reliability, only the highest quality components all UL listed or UL recognized are used. The cabinet is fabricated of heavy gauge reinforced steel with drip-proof hood. All field wiring and service connections may be made from the front, allowing the controller to be mounted flush against a wall.

The controller is completely wired, assembled, and tested at the factory before shipment, and ready for immediate installation.

The MP450 Series Autotransformer Fire Pump Controllers incorporate a heavy-duty autotransformer with taps available at 50%, 65%, and 80% to reduce the starting voltage to the motor. The autotransformer is factory wired to the 65% taps unless otherwise specified.

The starting inrush current drawn from the power source is reduced to approximately 25% of normal when using the 50% tap, 42% of normal on the 65% tap, and 64% of normal on the 80% tap (other taps are available, consult factory representatives for more information).

The timing between reduced voltage start and full voltage operation is field adjustable to accomodate specific installation requirements. An emergency start handle to close starting contactor independent of automatic control is also supplied as standard. When used, this handle will bypass the reduced voltage start feature and start the motor with full inrush current drawn from the power source.

Adobe Acrobat PDF Files

Drawings are provided in ADOBE pdf Format and are provided for reference only. Drawings and Specifications subject to change without notice. Drawings should not be used for construction. Contact our sales department for specific as-built drawings for your special project.

Outline and Hookup Drawings:

Without Transfer SwitchWith Transfer Switch
VoltageHP RangeOutlineHookupOutlineHookup
20015-20 CD33987BCH33697B CD33994D CH34015C
25-60CD34001BCH33697B CD34008C CH34017B
75-100 CD33783ACH34278 CD33817B CH33713B
125-150 CD33785A CH34278 CD33819B CH33713B
200-250CFCFCFCF
20815-20 CD33987BCH33697B CD33994D CH34015C
25-75CD34001BCH33697B CD34008C CH34017B
100 CD33783ACH34278 CD33817B CH33713B
125-150CD33785ACH34278 CD33819B CH33713B
200-250 CFCFCFCF
220-24015-25 CD33987BCH33697B CD33994D CH34015C
30-75CD34001BCH33697B CD34008C CH34017B
100-125 CD33783ACH34278 CD33817B CH33713B
150-200CD33785ACH34278 CD33819BCH33713B
250-300 CFCFCFCF
380-41515-40 CD33987BCH33697B CD33994D CH34015C
50-125CD34001BCH33697B CD34008C CH34017B
150-200 CD33783ACH34278 CD33817B CH33713B
250-300 CD33785ACH34278 CD33819BCH33713B
350 CFCFCFCF
440-48015-50 CD33987BCH33697B CD33994D CH34015C
60-150CD34001BCH33697B CD34008C CH34017B
200-250 CD33783ACH34278 CD33817B CH33713B
300-400 CD33785ACH34278 CD33819BCH33713B
500-600 CFCFCFCF
CF=Consult Factory

Sales Brochure:
MP450 Brochure

Suggested Specification
MP450 Suggested Specification

O&M Manual
O&M Manual for Microprocessor Electric Controllers
Spanish O&M Manual for Microprocessor Electric Controllers

Schematics:
MP450 Schematic Drawing Page 1
MP450 Schematic Drawing Page 2
MP450 Schematic Drawing with Transfer Switch Page 1
MP450 Schematic Drawing with Transfer Switch Page 2