Part Winding Start Type

Request more information about this product


Series MP420 - Combined Manual and Automatic

Metron Fire Pump Controllers conform to the latest requirements of Chapter 7, National Fire Protection Association Pamphlet 20, Standard for Centrifugal Fire Pumps, as adopted by Underwriters Laboratories and Factory Mutual. They are withstand rated and listed by Underwriters' Laboratories and approved by Factory Mutual Research Corporation.

Sizes range from 15 to 700 horsepower, 200 to 600 volts, 60 Hz. These controllers are for use on Across-the-Line type installations.

Only the highest quality components, all UL listed or UL recognized are used throughout to assure the best possible reliability. The cabinet is fabricated of heavy gauge reinforced steel with drip-proof hood. All field wiring and service connections may be made from the front, allowing the controller to be mounted flush against a wall.

The controller is completely wired, assembled, and tested at the factory before shipment, and ready for immediate installation.

The series MP420 fire pump controllers can be used when full voltage starting may not be desired or practical. The starting contactors operate in sequence to energize a portion of the motor windings on start which reduces inrush current to approximately 65% of normal. An adjustable timing relay is provided to control time between reduced current start and normal running operation. An emergency start lever to close starting contactor independent of automatic control circuits is also supplied as standard. When used, this lever will bypass the reduced current start feature and start the motor with full inrush current drawn from the power source.

Adobe Acrobat PDF Files

Drawings are provided in ADOBE pdf Format and are provided for reference only. Drawings and Specifications subject to change without notice. Drawings should not be used for construction. Contact our sales department for specific as-built drawings for your special project.

Outline and Hookup Drawings:

Without Transfer SwitchWith Transfer Switch
VoltageHP RangeOutlineHookupOutlineHookup
20015-60CD33984BCH33694B CD33991D CH34012C
75-150CD33774ACH34275 CD33808B CH33710B
200-250 CD33790A CH33759A CFCF
300CFCFCFCF
20815-75CD33984BCH33694B CD33991D CH34012C
100-150 CD33774ACH34275 CD33808B CH33710B
200-250CD33790A CH33759A CFCF
300 CFCFCFCF
220-24015-75CD33984BCH33694B CD33991D CH34012C
100-200 CD33774ACH34275 CD33808B CH33710B
250CD33790A CH33759A CFCF
300 CFCFCFCF
380-41515-125CD33984BCH33694B CD33991D CH34012C
150-300 CD33774ACH34275 CD33808B CH33710B
350-400CD33790A CH33759A CFCF
500 CFCFCFCF
440-48015-150CD33984BCH33694B CD33991D CH34012C
200-400 CD33774ACH34275 CD33808B CH33710B
500CD33790A CH33759A CFCF
600 CFCFCFCF
CF=Consult Factory

Sales Brochure:
MP420 Brochure

Suggested Specification
MP420 Suggested Specification

O&M Manual
O&M Manual for Microprocessor Electric Controllers
Spanish O&M Manual for Microprocessor Electric Controllers

Schematics:
MP420 Schematic Drawing Page 1
MP420 Schematic Drawing Page 2
MP420 Schematic Drawing with Transfer Switch Page 1
MP420 Schematic Drawing with Transfer Switch Page 2