The M15 Jockey (or make-up) Pump Controllers are in the same system as the main fire pump controller(s). Their purpose is to maintain normal water pressure and to help prevent unnecessary cycling of the main fire pump(s).
The M15 series Jockey Pump Controllers are listed to UL 508 Standard for Industrial Controls. Each controller contains an externally operable fuse disconnect switch with fuses which are horsepower rated, a motor contactor with protective overload relay, and a door mounted hand-off-auto switch all housed in a NEMA 2 drip proof enclosure. As an option, a circuit breaker is available in lieu of the fused disconnect.
The M15A, M15B, and M15C Jockey Pump Controllers include a 6-230 psi pressure switch with independent high and low set points for automatic starting and stopping. The pressure switch is piped to an external ?" NPT connector.
The M15A incorporates a control power transformer and run period timer.
The M15B omits the run period timer and the control power transformer.
The M15C incorporates a pneumatic timer thus eliminating the cost of a separate control power transformer.
Standard features of the M15A:
- Externally operable disconnect
- Horsepower rated fuses
- Hand-off-auto selector switch
- 10-300 psi pressure switch
- Control power transformer
- Minimum run period timer
- NEMA 2 Enclosure